대한전기학회:학술대회논문집 (Proceedings of the KIEE Conference)
- 대한전기학회 2006년도 춘계학술대회 논문집 전기설비전문위원
- /
- Pages.41-43
- /
- 2006
전위상승에 대한 독립접지방식과 공통접지방식의 비교
Comparison of Individual and Common Grounding Method for Potential Rise
- 길형준 (한국전기안전공사 전기안전연구원) ;
- 김동욱 (한국전기안전공사 전기안전연구원) ;
- 김동우 (한국전기안전공사 전기안전연구원) ;
- 이기연 (한국전기안전공사 전기안전연구원) ;
- 최충석 (한국전기안전공사 전기안전연구원)
- Gil, Hyoung-Jun (Electrical Safety Research Institute, subsidiary of KESCO) ;
- Kim, Dong-Ook (Electrical Safety Research Institute, subsidiary of KESCO) ;
- Kim, Dong-Woo (Electrical Safety Research Institute, subsidiary of KESCO) ;
- Lee, Ki-Yeon (Electrical Safety Research Institute, subsidiary of KESCO) ;
- Choi, Chung-Seog (Electrical Safety Research Institute, subsidiary of KESCO)
- 발행 : 2006.05.26
초록
This paper deals with a comparison of individual and common grounding method for potential rise. When a test current flowed through grounding electrode, potential rise was measured and analyzed for grounding method using a electrolytic tank in real time. The grounding electrodes were designed and fabricated with ground rods on a scale of one-eightieth. Potential rises of individual grounding method were higher than those of common grounding method. The distributions of surface potential are dependent on the distance from grounding electrode.
키워드