The Diagnosis of Cooling Tower System

Cooling Tower System 진동 진단

  • 이선휘 (케이티엠엔지니어링(주), 설비진단부)
  • Published : 2007.11.15

Abstract

The aim of this study is to estimate the cause of Cooling Tower vibration and eliminate the faults of fan with high vibration in spite of overhaul. The cause of high vibration was that the natural frequency of fan blade coincide with second blade pass frequency. To achieve reduction of Cooling Tower vibration, change motor speed from 1784rpm to 1714rpm, and then the vibration has reduced conspicuously.