Effects of Tape on Heat Transfer and Friction Factor in a Square Channel

사각 채널에 설치된 테이프가 열전달과 마찰계수에 미치는 효과

  • Published : 2007.05.30

Abstract

Heat transfer distributions and friction factors in square channels (3.5 ${\times}$ 3.5 cm) with twisted tape inserts and with twisted tape inserts plus interrupted ribs are respectively investigated. Tests are performed for Reynolds numbers ranging from 8,900 to 29,000. The rib height-to-channel hydraulic diameter, e/Dh, is kept at 0.057 and test section length-to-hydraulic diameter, L/Dh is 30. The twisted tape is 0.1 mm thick carbon steel sheet with diameter of 3.3cm, length of 90cm, and 2.5 turns. The square ribs are arranged to follow the trace of the twisted tape and along the flow direction defined as axial interrupted ribs. Each wall of the square channel is composed of isolated aluminum sections. The following conclusions from the experimental study were drawn as: 1) In the 4 heating wall channel with twisted tape inserts, Nusselt number based on bottom wall temperature is enhanced by 1.2 - 1.6 times if adding the axial interrupted ribs on the bottom wall only. 2) The twisted tape with interrupted ribs under the two-sided heating condition produces the highest heat transfer performance. 3) Friction factor data obtained for the square channel with twisted tape inserts plus axial interrupted ribs are less than those in the past publications for circular tubes with axial interrupted ribs and twisted tape inserts.