Characteristics of Lightning Impulse Current of ZnO Block for Transmission Line Arrester with External Gap

송전선로에 사용되는 갭형 피뢰기 소자의 뇌임펄스 전류특성

  • Published : 2007.06.21

Abstract

This paper describes the characteristics of lightning impulse current of ZnO block for transmission line arrester with external gap. The ageing parameters of lightning arresters are impulse current, moisture ingress, temperature ageing and so on. Especially it is important to estimate the change of electrical characteristics by impulse current. Total energy applied to the ZnO arrester each time is $4/10{\mu}s$, 30kA and $2/20{\mu}s$, 10kA impulse current. Before and After the test, the residual voltage variation of varistors passed was below 5%. According to the test, it is thought that the ZnO arrester shows good stability with impulse current test.

Keywords