An Analysis Method for the Transient Ground Impedance Using Variable Frequency Current and Lightning Impulse

가변주파수 및 임펄스 전류를 이용한 과도접지임피턴스 분석

  • Published : 2007.11.02

Abstract

This paper presents an analysis method of transient ground impedance using the lightning impulse and variable frequency currents. The transient ground impedance strongly depends on the configuration and size of grounding electrodes and the shapes of impulse currents, and the inductance of grounding electrodes has a significant affect on the transient impedance of the grounding system. There are some differences between the effective impulse ground impedance which was introduced some papers and the transient ground impedance. The transient ground impedance measured from the peak value of impulse voltage and the peak value of impulse current is more reliable than the effective impulse ground impedance.

Keywords