Experimental Study on the Drag Reduction & Heat Transfer Ratio in the Circular Pipe with Swirl Generater

난류발생기를 가지는 원형 파이프내에서의 마찰저감 및 열전달율에 관한 실험적 연구

  • Kim, Seong-Su (Graduate School, Jeonju University) ;
  • Cho, Sung-Hwan (Department of Mechanical and Automotive Engineering, Jeonju University) ;
  • Yoon, Seok-Mann (District Heating Technology Research Institute, Korea District Heating Corporation)
  • 김성수 (전주대학교 대학원) ;
  • 조성환 (전주대학교 기계자동차공학과) ;
  • 윤석만 (한국지역난방공사 기술연구소)
  • Published : 2008.06.25

Abstract

Total lengths of domestic pipe network for district heating system are above about 2,500Km. A lots of pumping power for heat transportation through long pipe are required by the flow friction of pipe surface. Until now there have been considered about various methods to reduce the flow friction for district heating system such as using surfactants and turbulence promoters by swirl flow and baffles etc. At this study, swirl flow generator was tested about the possibility to increase the heat transfer ratio at the heat exchanger in the case which the suppling water temperature increased from $50^{\circ}C$ until $120^{\circ}C$. Experimental results showed that the heat transfer ratio increased and also pressure increase ratio increased simultaneously in the case which swirl flow generator installed. The amount of the increasing ratio for heat transfer and pressure were reached until 4.33% and 11% at the case of $120^{\circ}C$ suppling temperature which domestic district heating system were using.