Selection of Ventilation Rate and Filter for a Residential Housing in View of Indoor Particle Concentration

공동주택의 적정 환기량 및 필터의 선정 - 실내입자농도를 중심으로 -

  • Published : 2008.06.25

Abstract

Ventilation rate and filter were selected to simultaneously satisfy indoor air quality and minimize energy consumption in residential housing. The concentrations of indoor particles were calculated using an adapted mass balance model for various ventilation airflow rates. To satisfy the guidelines for indoor concentrations of particles, the minimum ventilation rates of 1.0/h, 0.6/h and 0.4/h were required for MERV11, MERV13 and MERV14, respectively. And the fan power consumptions induced by ducts, a heat exchanger and a filter were calculated for various ventilation airflow rates. The increase in the ventilation rate caused a dramatic increase in the power consumption, but the filter performance did not have much of an effect on the fan power for ventilation airflow rates lower than 0.4/h. The use of the ventilation filter of MERV 14 was suggested at a ventilation rate of 0.4/h when the fan power consumptions were considered in addition to the indoor concentrations of particles and $CO_2$. The use of the MERV14 filter at a ventilation rate of 0.6/h could be more effective than the additional use of an indoor air cleaner when the residential housing unit was ventilated.