Air Flow Prediction and Experiment by T-Method According to Duct Layout on House Ventilation System

주택환기시스템의 덕트 Layout에 따른 T-Method의 풍량 예측 및 실험

  • Published : 2008.06.25

Abstract

The accurate distribution of flow rate has been a very important part to control the air change rate since introduction of house ventilation system. An inappropriate selection of fan due to incorrect prediction of pressure loss in duct brings energy loss. In the previous study the pressure loss of general spiral duct was measured and database was constructed for finding correct loss factors in fitting upper stream. The purpose of this study is to compare and investigate the error range of flow rate by applying T-Method to bilateral symmetry and asymmetry layout of duct. The results of this study are as following. It is demanded to decide accurate size under duct design for house ventilation system. Because the small amount of Flow rate was considered at that time. The error range was 3.17% on case1 and 3.52% on case2. The error range difference was 0.35%.