A study on the Cold-heat Storage System for Operation Status Monitoring of Showcase

쇼케이스 운전상태를 고려한 축냉시스템 적용타당성 연구

  • Lee, Eun-Ji (Geothermal Energy Research Center, Korea Institute of Energy Research) ;
  • Lee, Dong-Won (Geothermal Energy Research Center, Korea Institute of Energy Research)
  • Published : 2008.06.25

Abstract

Experimental study was performed to understand the operations of a showcase working in a discount store. Temperatures of evaporation, condenser were measured and also electric power consumption of compressor were measured. The purpose of this study is to application use of cold-heat storage systems operated the showcase. At the condition using ice storage system, the ice making process was operated during midnight being not needed the cooling of the showcase through the continuous running of the condenser unit. And then, the refrigerant was sub-cooled using stored cold-heat after being discharged from the air cooling condenser during the day time. The cooling performance was increased owing to the sub-cooling of refrigerant during day time, hence the running time of the compressor was effectively decreased. In other words, this study showed that power consumption during daytime can be transferred to the midnight for making use of the refrigerant sub-cooling. So the operating characteristics of the showcase system under various working conditions were analyzed and discussed.

Keywords