The optimal parameters in series-series counterflow chillers system within air conditioning

공조장치내의 직렬-직렬 대향류 냉각기에서 최적 변수

  • 웬민푸 (울산대학교 대학원) ;
  • 뷔옥훙 (호치민공대 기계공학과) ;
  • 이근식 (울산대학교 기계자동차공학부)
  • Published : 2009.06.25

Abstract

If water-chillers are arranged in series-series counterflow, compressor lift of each chiller will be decreased in comparison with water-chillers in parallel. That means that compressor power of the chillers in series will be lower than that of chillers in parallel. However, the pressure drop of the water flow through the chillers in series will increase, and thus increase the power of water pumps. This disadvantage will be made good by increasing the temperature difference of water flow through evaporator and condenser, but the water flow rates will decrease. This paper explores the optimal parameters in system of series-series counterflow for central chilled water plants such as the leaving chilled water temperature, the leaving condenser water temperature, condenser water flow rate and number of chillers in series.