고압전동기 고정자 권선의 절연파괴 특성
Characteristics of Insulation Failure in High Voltage Motor Stator Windings
- Kim, Hee-Dong (KEPCO Research Institute) ;
- Kim, Kyeong-Yeol (KEPCO Research Institute) ;
- Park, Deok-Hyun (Korea South-East Power Co.)
- 발행 : 2010.06.16
초록
Diagnostic tests were performed on six high voltage motors. These tests included ac current, dissipation factor(tan6) and partial discharge(PD) magnitude. The rewind of motor stator insulation at rated voltage is assessed by the results of these tests. After completing the diagnostic tests, the stator windings of motors were subjected to gradually increasing ac voltage, until the insulation punctured. No. 1 and No.2 motors(4.16 kV) failed near rated voltage of 12.3 kV and 14.2 kV, respectively. The breakdown voltage of No.3 and No.4 motors(6.6 kV) was 17.6 kV and 17.8 kV, respectively. These motors are higher that expected for good quality coils in 6.6 kV class motors.