HVAC 시스템의 중복고장 검출을 위한 실험적 연구

An Experimental Study on Multi-Fault Detection and Diagnosis Analysis of HVAC System

  • 조성환 (한국에너지기술연구원) ;
  • 홍영주 (충남대학교 기계설계공학과 대학원) ;
  • 양훈철 (한국에너지기술연구원) ;
  • 안병천 (경원대학교 건축설비공학과)
  • Cho Sung-Hwan (Building Energy Research Center, KIER) ;
  • Hong Young-Ju (Graduate School of Mechanical Design Engineering, ChungNam National University) ;
  • Yang Hooncheul (Building Energy Research Center, KIER) ;
  • Ahn Byung-Cheon (Department of Building Equipment System Engineering, Kyungwon University)
  • 발행 : 2004.10.01

초록

The objective of this study is to detect the multi-fault of HVAC system using a new pattern classification technique. To classify the effect of single-fault in determining the pattern, supply air temperature, OA-damper, supply fan, and air flowrate were chosen as experimental parameters. The combination of supply temperature, flow rate, supply fan and OA-damper were chosen as multi-fault conditions. Three kinds of patterns were introduced in the analysis of multi-fault problem. To solve multi-fault problem, the new pattern classification technique using residual ratio analysis was introduced to detect the multi-fault as well as single-fault. The residual ratio could diagnose single-fault or multi-fault into several patterns.

키워드

참고문헌

  1. Liu, S. T. and Kelly, G. E., 1989, Rule-based diagnostic method for HVAC fault detection, Proceeding of building simulation 89, Vancouver, pp.319-324
  2. Anderson, D., Grave, L., Reinert, W., Krei-der, J. F., Dow, J. and Wubbrna, H., 1998, A quasi-real-time expert system for com-mercial building HVAC diagnosis, ASHRAE Transactions, 95, pp. 954-960
  3. Pape, F. L. F., Mitchell, J. W. and Beckman, W. A., 1991, Optimal control and fault de-tection in heating, ventilating, and air-con-ditioning systems, ASHRAE Transactions, Vol. 97, No.1, pp.792-745.
  4. Norford, L. K., Rabl, A. and Soadaro, G. V., 1987, Energy management systems as di-agnostic tools for building managers and energy auditor, ASHRAE Transactions, Vol. 93, No.2, pp. 2360-2375
  5. Chen, B. and Braun, J. E., 2000, Simple fault packaged air conditioners, Proceedings of the Purdue University, West Lafayette, USA, July 25-28, pp.321-328
  6. Katipamula, S., Pratt, R. G., Shassin, D. P., Taylor, Z. T., Gwwiri, K. and Brambley, M. R., 1999, Automated fault detection and di-agnosis for outdoor-air ventilation systems and economizer, ASHRAE methodology and results from field Transactions, Vol. 105, pp. 555-567.
  7. House, J. M., Lee, W. Y. and Shin, D.R., 1999, Classification techniques for fault de-tection and diagnosis of an air-handling unit, ASHRAE Transactions, Vol. 105, pp.1087-1097
  8. Lee, W. Y, House, J. M., Park, C. and Kelly J. E., 1996, Fault diagnosis of an air-hand-ling system unit using artificial neural net-work, ASHRAE Transaction, Vol. 102, pp. 540-549
  9. Lin, C. T. and Lee, C. S. G., 1996, Neural Fuzzy Systems, Prentice-Hall International, Inc., p. 236