The vibration and noise characteristics analysis of Sound Insulation Panel for Transformer

변압기용 차음판의 진동 소음 특성 분석

  • 정한얼 (국립 경상대학교 대학원 정밀기계공학과) ;
  • 김효중 (국립 경상대학교 대학원 정밀기계공학과) ;
  • 구동식 (국립 경상대학교 대학원 정밀기계공학과) ;
  • 최병근 (국립 경상대학교 기계항공학부 해양산업연구소)
  • Published : 2006.11.30

Abstract

Recently, The demands for the reduction of noise generated by transformers have been increasing. Almost all of the noise generated by transformers is a result of magnetostricitive vibration in the core. The noise radiates into the atmosphere from the tank through the insulation oil. As the noise of transformer irritates residents, needs for decreasing the noise of transformer have been arised. One method of reduction such a noise is to build a free-standing enclosure of concrete and steel plates around the transformer. However, this method has some disadvantages. Another method of noise reduction is to mount a close-fitting sound insulation panel on the side of a transformer tank. Side plate vibrations of transformer are transmitted to such a sound insulation panel along two paths. In one case, they are transmitted through air by sound pressure and in the other through supporting structures. In the paper, the vibration and noise effect which is transferred from reinforce channel to insulation panel generated by transformer have been identified for the several kinds of insulation panel and damping sheet analytically and experimetally.

Keywords