보상 알고리즘을 적용한 변압기 보호용 전류차동 계전방식

Current Differential Relaying Algorithm for Power Transformer Protection Operating in Conjunction with a CT Compensating Algorithm

  • 강용철 (전북대 대학원 전기공학과) ;
  • 박종민 (전북대 대학원 전기공학과) ;
  • 이미선 (전북대 대학원 전기공학과) ;
  • 장성일 (전북대 대학원 전기공학과) ;
  • 김용균 (한국IED Eng.) ;
  • 소순홍 (전북대 대학원 전기공학과)
  • 발행 : 2007.11.01

초록

Current differential relays may maloperate during magnetic inrush and over-excitation because a significant differential current is produced. To prevent maloperation, the relays adopt some harmonic components included in the differential current. The harmonic restraints may increase the security of a relay but cause the operating time delay of a relay when an internal fault occurs. Moreover, the operating time delay is more increased if a current transformer (CT) is saturated. This paper describes a current differential relaying algorithm for power transformer protection with a compensating algorithm for the secondary current of a CT. The comparative study was conducted with and without the compensating algorithm. The performance of the proposed algorithm was investigated when the measurement CT (C400) and the protection CT (C400) are used. The proposed algorithm can compensate the distorted current of a CT and thus reduce the operating time delay of the relay significantly for an internal fault with CT saturation.

키워드

참고문헌

  1. A. G. Phadke and J. S. Thorp, 'Computer Relaying for Power Systems', Research Studies Press Ltd, 1988
  2. E. E. Conner, E. C. Wentz, and D. W. Allen, 'Methods for estimating transient performance of practical current transformer for relaying,' IEEE Trans. Trans. Power App. Syst., vol. PAS-94, pp. 116-122, Jan./Feb. 1975
  3. L. J. Powell, 'Current transformer burden and saturation,' IEEE Trans. Ind. Applicat., vol. IA -15, pp. 294-302, May/June 1979 https://doi.org/10.1109/TIA.1979.4503656
  4. IEEE Power System Relaying Committee, 'Transient response of current transformers,' IEEE Trans. Power App. Syst., vol. PAS-96, pp.1809-1811, Nov./Dec. 1977
  5. S. H. Horowitz and A. G. Phadke, Power System Relaying. Hertfordshire, UK.: Research Studies Press, pp. 56-57, 1992
  6. 'IEEE Guide for the application off current transformers used for protective relaying purposes'. IEEE standard C37.110-1996, 1996
  7. Y. C. Kang, J. K. Park, S. H. Kang, A. T. Johns and R. K. Aggarwal, 'An algorithm for compensating secondary currents of current transformers,' IEEE Trans. Power Delivery, Vol. 12, No.1, pp. 116-124, January 1997 https://doi.org/10.1109/61.568231
  8. Y. C. Kang, U. J. Lim, S. H. Kang and P. A. Crossley, 'Compensation of the distortion in the secondary current caused by saturation and remanence in a CT.' IEEE Trans. Power Delivery, Vol. 19, No.4, pp. 1642-1649, October 2004 https://doi.org/10.1109/TPWRD.2004.835266