연면방전에 의한 폴리머애자의 자외선 발생과 열화특성

The Characteristics of UV Generation and Aging Materials in According to Surface Discharge

  • 발행 : 2008.09.01

초록

Recently, The diagnosis techniques of electric facilities are developed on live line. This paper describes the discharge characteristics of polymer insulator(EPDM A type). Keeping the facilities in good working order, the goal of this paper will provide the information to enable user to easily judge conditions of facilities on the spot. The performance of polymer insulator is assessed from the KS C IEC 60270 and CEA LWIWG-01(96)(Tracking Wheel Test). As the results, UV generation patterns of polymer insulator grow like a jellyfish shape follow the ramping voltage. Discharging UVs are detected at about 31.25% of breakdown voltage. Just then, dimension of UV image is about $0.84cm^{2}$. The dimension of max. UV image is about $297.4cm^{2}$ at $160kV(V_{bd})$. The position of UV generation due to surface discharge of polymer insulator is the center of insulator in the early, then moved the ground side and the last, UV image moved through the junction part of source side. Surface of aged polymer insulator is cracked and faded due to arc. UV absorption spectrum of polymer insulator are appeared the C-H bond of scissoring vib. at $1014cm^{-1}$ and C=O bond of recombination structure. Also, recombined UV absorption peak such as C-H, N-H, and O-H is detected at the $3321cm^{-1}$. Through the paper, there are inspection data which are the relations between surface discharge of polymer insulator and UV detecting image.

키워드

참고문헌

  1. 송길목, 방선배, 김종민, 김선구, "자기애자에서의 코로 나 방전에 의한 자외선이미지 검출", KIEE HV&D spring conference, pp.2-13-2-16, 2007
  2. K.M. Shong, S.G. Kim, W.K. Han, Y.S. Kim, J.S. Jung and H.J. Choi, "Recognition and Detection of Corona Discharge on Porcelian Insulators at 22.9kV Distribution Line Using UV-Camera", 15th ISH2007, pp.439, 2007
  3. Kil-Mok Shong, Young-Seog Kim, Sun-Gu Kim, "Images Detection and Diagnosis of Corona Discharge on Porcelain Insulators at 22.9kV D/L", IEEE SDEMPED2007 Proc., pp.462-466, 2007
  4. EPRI, "Guide to Corona and Arcing Inspection of Substations", 2002
  5. EPRI, "Guide to Corona and Arcing Inspection of Overhead Transmission Lines", 2002
  6. Stanley Siu et al., "Utility of CHARM-2 in Diagnosing Sources of Plasma Charging Damage in High Density Etchers and in Assisting Hardware Development", 20027th IS on P&PID, pp.80-83, 2002
  7. Kohji Hohkawa, "Study on Photo-induced Acoustic Charge Transport Effect in GaN Film", IEEE 0-7803-8846-1/05, pp.421-424, 2005
  8. Stanislaw M Gubanski, Antonios E Vlastos, "Wettability of naturally aged silicone and EPDM composite insulators", IEEE Trans. on PD, Vol. 5, No. 3, pp.1527-1535, 1990
  9. Jen-Shih Chang, Phil A. Lawless, and Toshiaki Yamamoto, "Corona Discharge Processes", IEEE Trans. on PS, Vol. 19, No. 6, pp.1152-1166, 1991
  10. MA Bin, ZHOU Wenjun, WANG Tao, DING Yigong, "Study on Discharge Test under the Power Frequency Voltage of the Severe Non-uniform Electric Field Based on the UV-light Imaging Technology", CEEM'2006/Dalian, pp.253-259, 2006
  11. 이영근, "EPDM Polymer의 구조와 물성", 고무학회지 제27권 제3호, pp.215-223