DOI QR코드

DOI QR Code

영구자석형 동기발전기를 이용한 풍력단지의 플리커 저감

Flicker Mitigation in a Wind Farm by Controlling a Permanent Magnet Synchronous Generator

  • 발행 : 2009.12.01

초록

The power quality of wind energy becomes more and more important in connecting wind-farms to the grid, especially weak grid. This paper presents the simulation of a wind farm of a permanent magnet synchronous generator (PMSG) and a doubly fed induction generator (DFIG). Flicker mitigation is performed by using PMSG as a static synchronous compensator (STATCOM) to regulate the voltage at the point of common coupling (PCC). A benefit of the measure is that integrating two function of to control the active power flow and to reduce the voltage flicker in a wind farm. Simulation results show that controlling PMSG is an effective and economic measure in reducing the flicker during continuous operation of grid connected wind turbines regardless of short circuit capacity ratio, turbulence intensity and grid impedance angle.

키워드

참고문헌

  1. T. Sun, Z. Chen, and F. Blaabjerg, 'Flicker mitigation of grid connected wind turbines using STATCOM,' Power Electronics, Machines and Drives, 2004. (PEMD 2004). Second International Conference on (Com. Publ. No. 498), vol. 1,31, pp. 175-180, March-2ApriI2004
  2. A. Larsson, 'Flicker emission of wind turbines during continuous operation,' IEEE Trans. Energy Convers., vol. 17, no. 1, pp. 114-118, Mar. 2002 https://doi.org/10.1109/60.986447
  3. W. Hu, Shezen, Y Wang, and Z. Wang, 'Flicker study on variable speed wind turbines with permanent magnet synchronous generator,' Power Electronics and Motion Control Conference, 2008. EPE-PEMC 2008. 13th, pp. 2325-2330, Sep. 2008
  4. T. Sun, Shezen and F. Blaabjerg, 'Flicker study on variable speed wind turbines with double fed induction generators,' Energy Conversion, IEEE Transaction on, vol. 20, issue 4, pp. 896-905, Dec. 2005 https://doi.org/10.1109/TEC.2005.847993
  5. Y-S. Kim, A. Marathe, and D.-J. Won, 'Comparison of various methods to mitigate flicker level ofDFIG considering the effect of grid conditions,' KlEE Journal of Power Electronics, vol. 6, no. 1, Januruy 2006
  6. Y-S. Kim, A. Marathe, and D.-J. Won, 'Comparison of various methods to mitigate flicker level ofDFIG considering the effect of grid conditions,' KlEE Journal of Power Electronics, vol. 6, no. 1, Januruy 2006
  7. Electromagnetic Compatibility (EMC) - Part 4: Testing and Measurement Techniques - Section 15: Flickerrneter - Functional and Design Specifications, IEC Std. 610004-15, Nov. 1997
  8. Research Institute for Danish Electric Utilities (DEFU), Connection of Wmd Turbines to Low and Medium Voltage Networks, 2nd Ed., Research Institute for Danish Electric Utilities (DEFU), Oct. 1998
  9. ELTRA Transmission System Planning, Specifications for Connecting Wmd Farms to the Transmission Network, 2nd Ed., ELTRA Transmission System Planning, Apr. 2000
  10. B. Fox, D. Flynn, L. Btyans, N. Jenkins, D. Milborrow, M. O'OMalley, R Watson, and Olimpo Anaya-Lara, 'Wmd power integration - connection and system operational aspects' lET Power and Energy Series 50