DOI QR코드

DOI QR Code

The Reduction of Generator Output Calculation by Using 6σ Method on Steam Turbine Simulator in a Nuclear Power Plant

6시그마 기법을 적용한 원자력 터빈 시뮬레이터의 발전기 출력 연산오차 저감

  • Received : 2011.01.08
  • Accepted : 2011.01.08
  • Published : 2011.05.01

Abstract

This paper describes the improvement of the calculation by using $6{\sigma}$ method on steam turbine simulator in a nuclear power plant. The simulator is essential to not only verification and validation of control logic but also making sure of control constants in upgrading the long time used control system into the new one. And the dynamic model is a key point in that simulator. The model used during the retrofit period of the turbine controller in Kori Nuclear Power Plant makes difference in calculating generator output and control valve positions. That is because such operating data as the main steam pressure, the main steam temperature and control valve positions of Yongkwang #3 are different from those of Kori #4. Therefore, the model parameters must be tuned by using actual operating data for the high fidelity of simulator in calculating the dynamic characteristic of the model. This paper describes that the $6{\sigma}$ method is used in improvement of precision of generator output calculation in the steam turbine model of the simulator.

Keywords

References

  1. 박용성 "6시그마 품질혁신", 2004년 10월 중소기업청
  2. 최인규, 정창기 "680MW 원자력발전소 증기터빈 발전기의 부하차단 모의시험", 2007년도 대한전기학회 학술대회논문집, Vol.56, pp.1605-1606
  3. 최인규, 김종안, 박두용, 우주희, 신재호 "터빈 밸브시험중 충동실 압력제어에 의한 발전기 출력변동 최소화" 대한전기학회 논문집 Vol. 59, No. 1, 2010년 1월
  4. "원자력계통기초II(표준형)" 한국수력원자력 원자력교육원, 2008년, pp.113-114