DOI QR코드

DOI QR Code

Experimental Study on Heating Performance Characteristics of Air Source Heat Pump with Air to Water Type

공기열원 히트펌프의 난방 성능특성에 관한 실험적 연구

  • Lee, Kwon-Jae (Graduate School, Department of Mechanical Engineering, Sunmoon University) ;
  • Kwon, Young-Chul (Department of Mechanical Engineering, Sunmoon University) ;
  • Chun, Chong-Keun (Department of Mechanical Engineering, Sunmoon University) ;
  • Park, Sam-Jin (Department of Mechanical Engineering, Sunmoon University) ;
  • Kwon, Jeong-Tae (Department of Mechanical Engineering, Hoseo University) ;
  • Huh, Cheol (Korea Ocean Research and Development Institute)
  • Received : 2010.11.30
  • Accepted : 2011.04.27
  • Published : 2011.06.10

Abstract

This paper presents the heating performance characteristics of the air source heat pump with air to water type. The heating capacity, COP, P-h diagram were measured at various operating conditions, air-side temperatures, relative humidities, and inlet/outlet water temperature under the standard heating condition of KS B 6275. The experimental data for the heat pump were measured using the air-enthalpy calorimeter and the constant temperature water bath. As the air-side temperature increases, the heating capacity and COP increase. The effect of the air-side relative humidities on the heat pump performance is insignificant. The heat pump performance on inlet and outlet water temperatures and air-side temperatures(-7, -11, $-15^{\circ}C$) were studied. Heating capacity and COP increased about 27~39% with the air-side temperature increasing. Enthalpy between the front and the rear of condenser decreased about 6% by increasing of the inlet water temperature. These results can be utilized in the design of the air source heat pump system with air to water type.

Keywords

References

  1. Kwon, Y. C., Chun, C. K., Park, Y. C., Ko, K. W., and Seo, D. N., 2008, Experimental study on cooling performance of multi-heat pump by indoor-unit combination, Journal of the Korea Academia-Industrial cooperation Society, Vol. 9, No. 6, pp. 1487-1493. https://doi.org/10.5762/KAIS.2008.9.6.1487
  2. Kim, Y. J., Park, I. S., Kim, H. H., Youn, B., and Gil S. H., 2002, Development of a cycle simulation program for multi airconditioning systems using R410a, Journal of the Korea Academia-Industrial cooperation Society, Vol. 3, No. 3, pp. 210-215.
  3. Jung, G. H., Park, Y. C. and Oh, S. K., 2004, A study on performance characteristics of heat exchanger for heat pump with R410a refrigerant, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 16, No. 4, pp. 340-348.
  4. Kim, K. S., Kim, Y. G., Ryu, S. K., and Kim, T. J., 1995, Superheat control of evaporator by EEV, Proceedings of the SAREK 1995 Summer Annual Conference, pp. 296-301.
  5. Yosuke, Goto, 2008, Triple effect absorption chiller-heater, Refrigeration, Vol. 83, No. 5, pp. 29-34.
  6. Takashi, Aoyama, 2008, Absorption chiller-heater with auxiliary waste heat recovery, Refrigeration, Vol. 83, No. 5, pp. 35-41.
  7. Kwon, O. K., Cha, D. A., Yun, J. H., and Kim, H. S., 2009, A study on the heat transfer performance of evaporator heat transfer tube for absorption chiller, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 21, No. 4, pp. 215-221.
  8. KS B 6275, 2002, Reciprocating water-chillers.
  9. Lee, E. C., Baek, C. H., Kang, H., Kim, Y. C., Cho, H. H., and Cho, S. W., 2009, Experimental study on the performance of a C02 heat pump water heater, Korean Journal of Air-Conditioning and Refrigeration Engineering, Vol. 21, No. 6, pp. 367-372.

Cited by

  1. Spot Cooling System Development for Ever-bearing Strawberry by Using Low Density Polyethylene Pipe vol.56, pp.6, 2014, https://doi.org/10.5389/KSAE.2014.56.6.149