Floor Impact Noise Characteristics Depending on the Experimental Conditions Using Impact Ball

실험조건에 따른 임팩트 볼의 바닥충격음 변화 고찰

  • 이원학 (한국건설기술연구원 건축계획환경연구실) ;
  • 한찬훈 (충북대학교 건축공학과)
  • Received : 2010.12.20
  • Accepted : 2011.02.19
  • Published : 2011.02.28

Abstract

In Japan, bang machine has been considered to have problems about not only the impact force and frequency response which are different from the real impact sources such as children's jumping and running, but also damage in the wooden structure housing. Therefore, a new impactor for lower impact force to prevent demage in wooden structure housing was developed. The impact ball was adopted as the second standard impact source in JIS A 1418-2 and ISO 140-11. In the present study, floor impact sounds generated by impact ball with drop heights in four floors of mock-up building of Building Research Institute (BRI) similar to typical Japanese wooden structure housing were investigated and also compared to jumping sound. The results show that Impact ball sound dropped at 10 cm to 30 cm was most similar to jumping sound. And The impact sound levels at 250 and 500 Hz were more sensitive to drop height than other lower frequencies. The error that may occur from the difference of height of 10 cm up and down based on the standard drop height caused by the impact ball operated by human hands was approx. 1 dB or less only in its value of characteristic, but it must be carefully taken into Impact ball in the Korea Standard.

본 연구의 목적은 일본의 표준 중량충격원인 임팩트 볼을 국내의 표준중량충격원으로 도입시 바닥충격음 실험에 있어서 정확성에 대해 실험을 통해 알아보고자 했다. 이를 위하여 임팩트 볼을 이용하여 낙하 높이별, 가진위치를 바꾸어서, 수음점 높이에 대한 논의를 진행하였고, 임팩트 볼을 이용한 바닥충격음을 측정하고 이를 실제 충격원인 뛰는 충격음과 비교하여 실제 충격음과 가장 유사한 낙하 높이에 대한 검토를 실시하였다. 또한 일본 주택에서 주로 사용되고 있는 목구조와 국내 공동주택의 기본 구조인 콘크리트 구조에서의 바닥충격음 특성차이를 알아보기 위해 실험동에서 같은 조건으로 시험을 실시하여 시공재료 및 구법에 따른 차이를 알아보고자 하였다. 이에 대한 결과는 목구조에서는 낙하 높이가 10 cm에서 30 cm사이의 충격음이 실제 충격음과 비슷한 음압레벨을 갖는 것으로 나타났고 콘크리트 구조에서는 유사한 음압의 높이는 없었다. 또한 사람이 임팩트 볼을 운용하면서 표준낙하높이를 기준으로 상 하 10 cm 높이차로 생기는 오차는 역 A특성 값에서 약 1 dB이하 정도로 작은 오차를 나타내긴 하지만 우리나라에 표준 중량충격원으로 도입할 때에는 다양한 콘크리트 바닥구법에 따른 바닥충격음의 특성에 따른 적합한 임팩트 볼의 낙하 높이 및 측정 마이크로폰의 높이에 대한 고려는 신중히 하여야 한다.

Keywords

References

  1. 환경부, "2008 환경통계연감", 제 21호, 2008.
  2. 건설교통부, "공동주택 바닥충격음 차단구조인정 및 관리기준", 2004.
  3. H. Tachibana, H. Tanaka, M. Yasuoka, S. Kimura, "Development of new heavy and soft impact source for the assessment of floor impact sound insulation of buildings", Proceedings of Inter-noise 98, 1998.
  4. 정정호, 전진용, "임팩트 볼을 활용한 바닥충격음 측정 및 평가", 한국소음진동공학회 논문집, 제15권 제10호, 1160-1168쪽, 2005.
  5. Jin Yong Jeon, Jong Kwan Ryu, Jeong Ho Jeong, Hideki Tachibana, "Review of the Impact Ball in Evaluationg Floor Impact Sound", Acta Acustica United With Acustica, 2006.
  6. JIS 1418-2, "Acoustics - measurement of floor impact sound insulation of buildings. Part 2: Method using standard heavy impact source", Japanese Industrial Standards Committee, Tokyo. Japan, 2000.
  7. 日本建築學會, 建築物の遮音性能基準と設計指針 第二版, 技報堂 出版, 1999.
  8. Seung Yup Yoo, Sin Young Lee, Jin Yong Jeon, "The effect of sound field characteristics on the measurement of heavy-weight impact sound", 19th International Congress On Acoustics, 2007.
  9. ISO 140, "Acoustics - measurement of sound insulation in buildings and of building elements. Part 11: Laboratory measurements of the reduction of transmitted impact noise by floor coverings on light-weight framed standard floor", 2004.
  10. 이원학, 한찬훈, "SBR 라텍스 혼합 모르타르를 활용한 콘크리트슬라브의 바닥충격음 개선효과", 대한건축학회 제26권 4호, 79-86쪽, 2010.
  11. 이원학, 한찬훈, "SBR 라텍스 혼합모르타르를 활용한 바닥구조의 시공구법에 따른 바닥충격음 개선효과" 한국음향학회 학술발표대회논문집, 제29권 1호, 91-96쪽, 2010.
  12. Won-Hak Lee, Chan-Hoon Haan, "Floor Impact Noise Characteristics of Impact Ball Depending on the Drop Heights in the both Wooden and Concrete Structures", ICA2010, Proceedings of 20th International Congresson Acoustics, pp. 583-587, 2010.
  13. 이원학, 한찬훈, "낙하높이에 따른 임팩트 볼의 바닥충격음 특성", 한국음향학회 학술발표대회논문집, 제29권 2호, 63-68쪽, 2010.