Abstract

The on-line partial discharge (PD) in stator windings of air-cooled gas turbine (GT) generator (119.2MVA, 13.8kV) is measured and analyzed in this paper. This generator was designed by global vacuum pressure impregnation (VPI). The generator failed two times at top bar (16T) of phase B in the stator slot. Six epoxy-mica capacitors were installed in three phases of GT generator. On-line PD test was performed on GT generator using turbine generator analyzer (TGA). TGA showed that the normalized quantity number (NQN) and the PD magnitude($Q_m$) were high in phase B. Internal discharges were generated in phases A, B and C. The trend analysis of NQN and $Q_m$ value are obtained in order to monitor the insulation condition in GT generator stator windings. Phases A and C were in good condition. But phase B had deteriorated significantly

Keywords

References

  1. R. Morin, R. Bartnikas and P. Menard, "A Three-Phase Multi-Stress Accelerated Electrical Aging Test Facility for Stator Bars", IEEE Trans. on Electrical Conversion, Vol. 15, No. 2, pp. 149-156, 2000. https://doi.org/10.1109/60.866992
  2. G. Griffith, S. Tucker, J. Milsom and G. C. Stone, "Problems with Modern Air-Cooled Generator Stator Winding Insulation", IEEE Electrical Insulation Magazine, Vol. 16, No. 2, pp. 6-10, 2000.
  3. Hee-Dong Kim, Byong-Han Kim, "Properties of On-Line Partial Discharge in Hydrogenerator Stator Windings", The Transactions of KIEE, Vol. 55C, No. 4, pp. 172-177, 2006.
  4. Jeong-Ho Chang, Dong-Keun Lee, Heung-Ho Lee, "Site Evaluation and Application of the On-line and Off-line Test for the 13[kV] Class Hydropower Generator Stator Windings", Journal of the KIIEE, Vol. 25, No. 11, pp. 73-82, 2011. https://doi.org/10.5207/JIEIE.2011.25.11.073
  5. W. McDermid and J. C. Bromley, "Experience with Directional Couplers for Partial Discharge Measurements on Rotating Machines in Operation", IEEE Trans. on Energy Conversion, Vol. 14, No. 2, pp. 175-181, 1999. https://doi.org/10.1109/60.766981
  6. G. C. Stone, T. E. Goodeve, H. G. Sedding and W. McDermid, "Unusual PD Pulse Phase Distributions in Operating Rotating Machines", IEEE Transactions on Dielectrics and Electrical Insulation, Vol. 2, No. 4, pp. 567-577, 1995. https://doi.org/10.1109/94.407022
  7. Hee-Dong Kim, Gyu-Hyun Yang, Young-Ho Ju, "Assessment of Insulation Condition in Gas Turbine Generator Stator Windings", The Transactions of KIEE, Vol. 59, No. 8, pp. 1423-1428, 2010.
  8. G. C. Stone, Partial Discharge Seminar, Iris Power Engineering Inc., Vol. 1, pp. 56-78, 2005.
  9. G. C. Stone and V. Warren, "Objective Methods to Interpret Partial-Discharge Data on Rotating-Machine Stator Windings", IEEE Trans. on Industry Applications, Vol. 42, No. 1, pp. 195-200, 2006. https://doi.org/10.1109/TIA.2005.861273