DOI QR코드

DOI QR Code

극한 환경 시험을 위한 극저온 챔버의 CFD 해석 및 에너지 효율 평가에 관한 연구

A Study on the CFD Analysis and Estimation of the Energy Efficiency of Cryogenic Chamber for Extreme Climate Test

  • Kang, Yul-Ho (School of Mechanical Engineering, Pusan National University) ;
  • Kim, Min-Kyu (School of Mechanical Engineering, Pusan National University) ;
  • Park, Warn-Gyu (School of Mechanical Engineering, Pusan National University)
  • 투고 : 2015.09.30
  • 심사 : 2016.01.14
  • 발행 : 2016.02.10

초록

There are many types of national and international standards for low temperature tests depending on the products. This study conducted CFD analysis and estimation of the energy efficiency of the chamber both with and without a test object by considering variations of COP and specific volume according to temperature. The supply air was located in the upper area to compare the cooling performance for each location using various outlets in mixed ventilated conditions. For cases without the test object, the air temperature of the upper supply and center extract on the opposite side type chamber cooled faster than other areas by 4.3~29.8%. However, for cases with the test object, the object temperature of the upper supply and lower extract type chamber cooled faster than the other areas by 7.2~31.5%. The cooling efficiency of the air inside the chamber and the test object did not show the same pattern, which indicates the need to consider the cooling performance by not only the air but also the test object in the cryogenic chamber design for testing.

키워드

참고문헌

  1. Kolesnikov, A., 2006, Use of Computational Fluid Dynamics to Predict Airflow and Contamination Concentration Profiles within Laboratory Floor Plan Environment, Applied Biosafety, Vol. 11, No. 4, pp. 197-214. https://doi.org/10.1177/153567600601100411
  2. Emmerich, S. J. and McGrattan, K. B., 1998, Application of a Large Eddy Simulation Model to Study Room Airflow, ASHRAE Transactions, Vol. 104, No. 1, pp. 1-9.
  3. Gan, G., 1995, Evaluation of room air distribution systems using computational fluid dynamics, Energy and Buildings, Vol. 23, No. 2, pp. 83-93. https://doi.org/10.1016/0378-7788(95)00931-0
  4. Cao, G. et al., 2014, A review of the performance of different ventilation and airflow distribution systems in buildings, Building and Environment, Vol. 73, No. 3, pp. 171-186.
  5. Posner, J. D. et al., 2003, Measurement and prediction of indoor air flow in a model room, Energy and Buildings, Vol. 5, No. 5, 2003, pp. 515-526.
  6. Horikiri, K. et al., 2011, Numerical Simulation of Convective Airflow in an Empty Room, International Journal of Energy and Environment, Vol. 5, No. 4, pp. 574-581.
  7. Zhao, L. et al., 1999, Measurement of airflow patterns in ventilated spaces using particle image velocimetry, An ASAE Meeting Presentation, Paper No. 994156.
  8. Liang, Y. Y. et al., 2014, A transient thermal model for full-size vehicle climate chamber, Energy and Buildings, Vol. 85, pp. 256-264 https://doi.org/10.1016/j.enbuild.2014.09.020
  9. Lee, T.-S. et al., 2006, Thermodynamic analysis of optimal condensing temperature of cascade-condenser in $CO_2/NH_3$ cacade refrigeration systems, International Journal Refrigeration, Vol. 29, pp. 1100-1108. https://doi.org/10.1016/j.ijrefrig.2006.03.003
  10. Zuo, W. and Chen, Q., 2009, SReal time or fasterthan- real-time simulation of air flow in buildings, Indoor Air, Vol. 19, No. 1, pp. 33-44. https://doi.org/10.1111/j.1600-0668.2008.00559.x
  11. Nam, Y. et al., 2011, Study on Non-uniform Thermal Comfort in Hybrid Air-Conditioning System with CFD Analysis, Korean Journal Of Air-Conditioning and Refrigeration Engineering, Vol. 23, No. 3, pp. 216-222. https://doi.org/10.6110/KJACR.2011.23.3.216