Abstract
In this study, the characteristic lifetime of power facilities such as power transformers and GIS were investigated as the basis of power facility asset management. It is difficult to obtain the operation and failure data of the facilities in Korea. Therefore, the number of failures of the electric power facilities was calculated from the operation data and hazard rate shown in the overseas literatures, and the statistical analysis was performed using the Weibull distribution function. As a result of extracting and analyzing the data of the UK National Grid for power transformers, the characteristic lifetime (scale parameter) of 116.45 years was considered to be a very appropriate value for power transformer management and can be used as a comparative data of the analysis of the domestic transformers. As for the GIS, based on the Bays and Bay-Years data and the hazard rate according to the operation years of the 123kV GIS in Germany, it is found out that the characteristic lifetime of GIS is not so meaningful. It is necessary to decide a maintenance strategy and lifetime expectancy considering the characteristics of the design, materials and manufacturing process of GIS.