A study on Measurement and Improvement of Indoor Air Quality in Dental Clinic

  • Choi, Mi-Suk (Dept. of Dental Hygiene, Chodang University) ;
  • Ji, Dong-Ha (Dept. of Environmental Health, Daejeon Health Institute of Technology)
  • 투고 : 2018.08.20
  • 심사 : 2018.10.22
  • 발행 : 2018.11.30

초록

The purpose of this study is to propose a management method to maintain the pleasant indoor air quality of the dental clinic by measuring and analyzing the indoor air quality of the dental clinic. The measurement was conducted in two rooms, a lobby where many residents stay in the reception room for waiting for medical treatment, and a VIP room where treatment activities are mainly performed. Measurement items are Temperature, Humidity, $CO_2$, CO, $NO_2$, $CH_2O$, VOC, $PM_{10}$ and measurement were taken on April 27, 2018. As a result of analyzing the temperature and humidity of the dental clinic, it was analyzed that the average indoor temperature was maintained at $25^{\circ}C$ and the humidity was kept at around 50%, maintaining proper indoor temperature and humidity environment. $CO_2$ was 855ppm in the VIP Room, which satisfied the maintenance standard. In the case of the lobby, it was analyzed to be 1,160ppm, which exceeded the maintenance standard and it is judged that the carbon dioxide generated by the respiration of the people staying in the lobby is the main reason. The mean concentration of formaldehyde in the VIP room was analyzed as $436{\mu}g/m^3$, exceeding the maintenance standard, and $2,100{\mu}g/m^3$ for the VOC exceeded the recommended standard. It was analyzed that the concentration was relatively higher due to the use of disinfectant and other drugs. The mean concentration of PM-10 in the lobby was analyzed as $65{\mu}g/m^3$ and it was analyzed that it satisfied the maintenance standard. To maintain a pleasant indoor air quality in a dental clinic it is necessary to minimize the effects of formaldehyde, VOC, $CO_2$ in the VIP rooms and lobby. For this purpose, the entire ventilation system and air purification system of the dental clinic should be installed. In case of the VIP room, local exhaust ventilation should be installed and workers should wear personal protective equipment.

키워드

CPTSCQ_2018_v23n11_143_f0001.png 이미지

Fig. 2. Concentration change of carbon dioxide with time(VIP Room)

CPTSCQ_2018_v23n11_143_f0002.png 이미지

Fig. 3. Concentration change of HCHO with time (VIP Room)

CPTSCQ_2018_v23n11_143_f0003.png 이미지

Fig. 4. Concentration change of VOC with time (VIP Room)

CPTSCQ_2018_v23n11_143_f0004.png 이미지

Fig. 5. Concentration change of carbon dioxide with time(Lobby)

CPTSCQ_2018_v23n11_143_f0005.png 이미지

Fig. 6. Concentration change of PM10 with time(Lobby)

CPTSCQ_2018_v23n11_143_f0006.png 이미지

Fig. 7. Concentration change of VOC & HCHO with time(VIP Room)

CPTSCQ_2018_v23n11_143_f0007.png 이미지

Fig. 1 Measuring Scene

Table 1. Measurement items

CPTSCQ_2018_v23n11_143_t0001.png 이미지

Table 2. Results of temperature and humidity measurement (VIP Room)

CPTSCQ_2018_v23n11_143_t0002.png 이미지

Table 3. Carbon dioxide measurement result(VIP Room)

CPTSCQ_2018_v23n11_143_t0003.png 이미지

Table 4. HCHO measurement result(VIP Room)

CPTSCQ_2018_v23n11_143_t0004.png 이미지

Table 5. VOC measurement result(VIP Room)

CPTSCQ_2018_v23n11_143_t0005.png 이미지

Table 6. Results of temperature and humidity measurement (Lobby)

CPTSCQ_2018_v23n11_143_t0006.png 이미지

Table 7. CO2 measurement result(Lobby)

CPTSCQ_2018_v23n11_143_t0007.png 이미지

Table 8. PM10 measurement result(Lobby)

CPTSCQ_2018_v23n11_143_t0008.png 이미지

Table 9. Measurement result(VIP Room, Lobby)

CPTSCQ_2018_v23n11_143_t0009.png 이미지

참고문헌

  1. Ministry of Environment, "Indoor air quality management, act", 2018.
  2. JACho, "A study on the working safety recognition and chemical hazard recognition," J. Kor. Soc. Cosm, Vol. 13, No. 3, pp. 1028-1039, March 2017.
  3. Ministry of Environment, "Indoor air quality management, Regulation," 2018.
  4. NHKim, KWooMin, GWCho, DJSeo, KHIm, WSJeung, YGCho, JSYang, "Health effects on workers and actual exposure of VOCs in the nail shops," Journal of Korean Society of Occupational and Environmental Hygiene, Vol. 27, No. 1, pp. 59-69, March 2017. https://doi.org/10.15269/JKSOEH.2017.27.1.59
  5. MSChoi, "The satisfaction and subjective symptom level by indoor air quality in dental parlor in Capital and Jeon-nam area," Journal of Korean society of Dental Hygiene, Vol. 11. No. 3, pp. 405-417, June 2011.
  6. YHLee, YJChoi, JOChoi, "Convergence Evaluation of Indoor Air Measurement in Medical Institution," Journal of the Korea Convergence Society, Vol. 8. No. 1, pp. 71-76, Jan. 2017. https://doi.org/10.15207/JKCS.2017.8.1.071
  7. BRLee, JHKim, KSKim, HJKim, KYLee, "Assessment of Thermal Comfort in a General Hospital in Winter Using Predicted Mean Vote (PMV)," J Environ Health Science, Vol. 41. No. 6, pp. 389-396, Nov. 2015.
  8. MHKim, JHKim, OHKwon, YJSeok, JWJeong, "Energy Saving Potentials of a Dedicated Outdoor Air System in a Healthcare Facilities," Korea Institute of Architectural Sustainable Environment and Building Systems, pp. 142-146, 2010.
  9. YHPark, SWKim, HHYang, OKChung, SJLee, "Kids Cafe Indoor Air Quality Analysis Based on Furniture and Installation Facilities," Journal of the Korea Furniture Society, Vol. 24, No.1, pp. 70-78, Jan. 2013.
  10. JUWon, "Health Effects of Chemicals used in hospitals among Healthcare Workers," J Korean Med Assoc, Vol. 53. No. 6, pp. 474 - 482, 2010. https://doi.org/10.5124/jkma.2010.53.6.474
  11. SYCho, JYYang, YYLim, KHShin, DCShin, "An Analysis about Building-related Health Symptoms of Workers at Dental College Hospitals in Seoul," J. ENVIRON. TOXICOL, Vol. 24. No. 2, pp. 149-157, 2009.
  12. MJPark, "A Study on Hospital Architecture of Indoor Air Quality Improvement and Harmful factors Management plan," RESIDENTIAL ENVIRONMENT : JOURNAL OF THE RESIDENTIAL ENVIRONMENT INSTITUTE OF KOREA, Vol. 12. No. 2, pp. 43-53, June 2014.
  13. NNJeong, HWLee, JRSohn, "Evaluation of Utilization on Air Quality Measuring Sensors Based on Internet of Things (IoT) for Indoor Air Quality Management at Hospital," ARCHITECTURAL INSTITUTE OF KOREA, Vol. 38. No. 1, pp. 466-466, April 2018.