DOI QR코드

DOI QR Code

Comparison of Three Active-Frequency-Drift Islanding Detection Methods for Single-Phase Grid-Connected Inverters

  • Kan, Jia-rong (Department of Electrical Engineering, Yancheng Institute of Technology) ;
  • Jiang, Hui (Department of Electrical Engineering, Yancheng Institute of Technology) ;
  • Tang, Yu (Department of Electrical Engineering, Hebei University of Technology) ;
  • Wu, Dong-chun (Department of Electrical Engineering, Yancheng Institute of Technology) ;
  • Wu, Yun-ya (Department of Electrical Engineering, Yancheng Institute of Technology) ;
  • Wu, Jiang (Suzhou Power Supply Company, National Grid Jiangsu Electric Power Co.)
  • Received : 2018.07.15
  • Accepted : 2018.11.10
  • Published : 2019.03.20

Abstract

A novel islanding detection method is proposed in this paper. It is based on a frequency drooping PLL, which was presented in a previous work. The cause of errors in the non-detection zone (NDZ) of conventional frequency disturbance islanding detection methods (IDM) is analyzed. A frequency drooping phase-locked-loop (FD-PLL) is introduced into a single-phase grid-connected inverter (SPGCI), which can guarantee that grid current is in phase with the grid voltage. A novel FD-PLL IDM is proposed by improving this PLL. In order to verify the performance of the proposed FD-PLL IDM, a full performance comparison between the proposed IDM and typical existing active frequency drift IDMs is carried out, which includes both dynamic performance and steady performance. With the same NDZ, the total harmonic distortion of the grid-current in the dynamic process and steady state is analyzed. The proposed FD-PLL IDM, regardless of the dynamic or steady process, has the best power quality. Experimental and simulation results verify that the proposed FD-PLL IDM has excellent performance.

Keywords

I. INTRODUCTION

In distributed generation (DG) systems, the islanding protection function is mandated according to IEEE 929 and 1547 standards [1], [2]. If islanding operation occurs and a DG is not broken away from the utility grid in a timely manner, there are a number of negative impacts on the network and the DG itself, such as safety hazards to utility personnel and the public, power quality problems, and serious damage to the utility grid and DG systems [3], [4]. Another condition is when a DG system is operated in the islanding mode after a power failure, which makes it necessary for the DG system to break away from the grid utility [4]. Therefore, researchers have been working to seek an islanding detection method (IDM) without a non-detection zone (NDZ) or with small NDZ [5]. NDZs can be defined as loading conditions for which an IDM fails to operate in a timely manner. However, some IDMs known as ‘no NDZ’ depend on the control performance of a single-phase grid-connected inverter (SPGCI) in practical operation [6].

IDMs can be classified into three categories: ① passive IDMs, ② active IDMs and ③ communication-based IDMs. The conventional passive IDMs generally detect the amplitude or frequency of the voltage at the point of common coupling (PCC) and suffer from a larger NDZ when compared with active IDMs. The novel passive IDM in [7] detects ripple voltage at the switching frequency to determine islanding, which utilizes different impedance characteristics in both the grid-tied mode and the islanding mode. However, accurate and quick detection of ripple voltage at the switching frequency is hard work for digital signal processor (DSP).

The communication-based IDMs modulate the utility voltage signal into the power line through an additional device. Therefore, communication-based IDMs have almost no NDZ. The shortcomings of this method are its high cost and the fact that it is fitted for micro-grids composed of a lot of DG systems [8].

Active IDMs [9] have been widely researched and used due to their small NDZ and low cost. A certain parameter disturbance is injected into the system and then the controller detects the PCC voltage to determine whether the grid is operated under the normal condition. These disturbance parameter injections can be composed of current [10]-[12], active or reactive power [13], [14], frequency [15]-[19], etc. It is believed that frequency parameter disturbances cause the least problems with respect to transient response and power quality at high penetration levels due to the fact that the frequency tends to be a very tightly regulated parameter in power systems when compared with the amplitude and phase [19].

The frequency parameter disturbance active IDMs include active frequency drift (AFD) [15], slide-mode frequency shift (SMS) [16] and Sandia frequency shift (SFS) [17]-[19]. The SMS and SFS methods are widely used due to their small NDZ [15]. The disturbance parameter must be increased if a smaller NDZ is needed, which degrades the power quality of the grid-current [13]. Moreover, some inherent problems [20], such as the phase difference between the grid-voltage and the grid current, affect the accuracy of the NDZ and its causation is analyzed in this paper. To obtain a new active IDM with a small NDZ and a high power quality, a method based on a frequency drooping phase-locked-loop (FD-PLL) has been proposed. When compared with SMS and SFS IDMs, the proposed FD-PLL IDM appears to be less affected by phase differences and the inverter has the best power quality in both the dynamic process and the steady state.

The paper is organized as follows. Section II analyzes the cause of NDZ errors in conventional SMS and SFS IDMs. Section III presents the FD-PLL to overcome the phase detecting time delay, and a phase disturbance is introduced into the FD-PLL to form a new FD-PLL IDM. Section IV analyzes the power quality of a SPGCI controlled by different IDMs with the same NDZ. Simulation results are given in Section V. Finally, some conclusions are given in Section VI.

II. NDZ ERRORS OF SMS AND SFS IDMS

A. SPGCI and its Control Strategy

According to the IEEE Standard 929–2000, a non-isolated inverter is one that ceases to energize the utility line under certain conditions using a test circuit with a parallel RLC load, as shown in Fig. 1(a), where the DC bus voltage UD is supplied by a renewable resource, Lf is the filter inductor, uG and iG are the grid voltage and current, and uPCC is the PCC voltage. The SPGCI can achieve a unity power factor through an appropriate control strategy.

E1PWAX_2019_v19n2_509_f0001.png 이미지

Fig. 1. Circuits used for assessing the anti-islanding features of a SPGCI and its control diagram. (a) Circuit topology. (b) Control diagram.

Fig. 1(b) shows a control block diagram of a SPGCI with grid voltage feed-forward control, where IG* and iG-u are the amplitude and phase of the reference grid current iG. In addition, iG* is the reference value of iG, and kp and ki are the proportional and integral parameter of the current-loop. Furthermore, KPWM and KN are the inverter voltage gain and the grid-voltage feed-forward coefficient, respectively. Note that the PLL detects the frequency of the grid voltage (fG) and the phase information.

B. Cause of Phase Difference between uPCC and iG

If KN = 1/ KPWM, the grid current iG is affected by the grid voltage, and the closed-loop transfer function is as follows:

\(i_{G}(s)=\frac{K_{P W M} k_{p} s+K_{P W M} k_{i}}{L_{f} s^{2}+K_{P W M} k_{p} s+K_{P W M} k_{i}} i_{G}^{*}(s)\)       (1)

If the PLL can guarantee that the reference current iG* is in phase with uPCC, the phase difference (θlag) between uPCC and iG can be expressed as (2) after the Laplace variable ‘s’ is substituted by ‘jω’.

\(\theta_{\text {lag}}=\frac{\omega^{3} L_{f} K_{P W M} k_{p}}{\omega^{2} K_{P W M}^{2} k_{p}^{2}-\omega^{2} L_{f} K_{P W M} k_{i}+K_{P W M}^{2} k_{i}^{2}}\)       (2)

According to (2), Lf, kp and ki can affect the value of θlag. In [20], the curves for θlag with different parameters are given. Therefore, theoretically, the phase difference between uPCC and iG is inevitable without attaching an additional phase compensation method. Moreover, if the phase detection time delay of the PLL is considered, θlag cannot be ignored.

C. NDZ Error of SMS IDM

The SMS IDM applies positive feedback to the phase of the voltage at the PCC by changing the phase of iG*[15].

\(i_{G_{-} \operatorname{SMS}_{-}k}^{*}=I_{G}^{*} \sin \left(2 \pi f_{P C C_{-} k-1} t+\theta_{\mathrm{SMS}}\right)\)       (3)

\(\theta_{S M S}=\theta_{m} \sin \left(\frac{\pi}{2} \frac{f_{P C C}-f_{G}}{f_{m}-f_{G}}\right)\)       (4)

where fpcc-k−1 is the grid frequency in the last line cycle, fm is the frequency when the maximum phase shift θm occurs, and fG is the rated frequency of the utility grid.

To the parallel RLC load, its quality factor Qf and phase angle θload are:

\(Q_{f}=2 \pi f_{r} R C=\frac{R}{2 \pi f_{r} L}=R \sqrt{\frac{C}{L}}\)       (5)

\(\theta_{\text {load}}=\arctan \left[Q_{f}\left(\frac{f_{r}}{f}-\frac{f}{f_{r}}\right)\right]\)       (6)

where fr is the resonant frequency of the load and its value is \(\sqrt{1/LC}/2 \pi\).

According to the analysis mentioned in Section II-B, there is a phase difference θlag between iG* and iG. Thus:

 

Therefore, θlag counteracts a part of the function of θSMS. The sketch of the phase angle is shown in Fig. 2 with the parameters shown in Table I. When θlag=0, as shown in Fig. 2(a), the PCC frequency may stabilize at point A1 or A2 after islanding occurs, which is determined by the initial polarity of (θSMS + θload). However, if θlag≠0, as shown in Fig. 2(b), the condition is quite different from that of θlag=0. When the initial frequency is at point A4 after islanding, the PCC frequency finally stabilizes at point A3 because the initial value of (θSMS + θload - θlag) is less than zero. However, when the initial frequency is at point A5, the frequency at the PCC finally stabilizes at point A6 because the initial value of (θSMS + θload- θlag) is greater than zero. It can be seen that the frequency at point A6 is less than that at point A2. The final frequency can be located in the normal frequency range if θlag is big enough. This shows that the range of the NDZ can be affected by the phase θlag.

E1PWAX_2019_v19n2_509_f0002.png 이미지

Fig. 2. Phase angle sketch of different conditions. (a) θlag=0°. (b) θlag=1°.

TABLE I LOAD AND DISTURBANCE PARAMETERS

E1PWAX_2019_v19n2_509_t0001.png 이미지

The rule for plotting the NDZ is (θload – θlag + θSMS)=0. Therefore, according to [6], it is possible to obtain:

\(f_{r}^{2}+\frac{f_{P C C} \tan \left(\theta_{S M S}-\theta_{l a g}\right)}{Q_{f}} f_{r}-f_{P C C}^{2}=0\)       (8)

To achieve the NDZ of the SMS IDM when θlag≠0, the islanding frequency is first adjusted to the threshold frequency (49.3 or 50.5). NDZs with θlag=0 and θlag=2° are shown in Fig. 3. It can be seen that the NDZ of θlag=0 is smaller in size than that of θlag≠0°. Moreover, the NDZ deviates from the routine analysis in many studies [15] when θlag≠0°.

E1PWAX_2019_v19n2_509_f0003.png 이미지

Fig. 3. NDZ with consideration of θlag.

D. NDZ error of SFS IDM

The reference current of an inverter using the SFS IDM is:

\(i_{G_{-} S F S_{-} k}^{*}=I_{G}^{*} \sin \left[2 \pi\left(f_{P C C_{-} k-1}+\Delta f\right)\right] t\)       (9)

The relationship between the voltage and the current is shown in Fig. 4.

E1PWAX_2019_v19n2_509_f0004.png 이미지

Fig. 4. Current and voltage waveforms in the SFS IDM.

In a half line cycle, the time interval of the zero current is tz. Therefore, the phase θSFS, where the grid current leads the PCC voltage, is equal to πPCCtz. The truncation factor cf is defined as:

\(c_{f}=2 f_{P C C} t_{z}=\frac{2 \theta_{S F S}}{\pi}\)       (10)

\(t_{z}=\frac{1}{f_{P C C_{-} k-1}}-\frac{1}{f_{P C C_{-} k-1}+\Delta f}=\frac{\Delta f}{f_{P C C_{-} k-1}\left(f_{P C C_{-} k-1}+\Delta f\right)}\)       (11)

According to [17], the truncation factor cf is:

\(c_{f}=k\left(f_{P C C_{-} k-1}-f_{G}\right)\)       (12)

Therefore, θSFS becomes:

\(\theta_{S F S}=\frac{\pi}{2} k\left(f_{P C C_{-} k-1}-f_{G}\right)\)       (13)

Like the condition in the SMS IDM, the rule for plotting the NDZ is that (θload–θlagSFS)=0. Thus, the NDZ of the SFS IDM is similar with that of the SMS IDM when θlag≠0. Therefore, it is not repeated here.

III. FREQUENCY DROOPING PLL AND FD-PLL IDM

A. Frequency Drooping PLL

The error NDZ is caused by the phase angle θlag between uPCC and iG. This phase angle θlag is difficult to eliminate since it is an open-loop controlled parameter. In order to realize θlag=0, this parameter must be introduced into the control.

Fig. 5(a) shows the FD-PLL for a SPGCI. When compared with the PLL used in Fig. 1(b), the FD-PLL has the frequency drooping characteristic. Setting γ is that the phase angle where the grid current iG is ahead of the PCC voltage uPCC. Therefore:

\(\gamma=-\theta_{l a g}\)       (14)

E1PWAX_2019_v19n2_509_f0005.png 이미지

Fig. 5. Control block diagram based on a FD-PLL and an equivalent control block diagram of the FD-PLL. (a) Control block diagram. (b) Equivalent control block.

The frequency of iG* is determined by the frequency of uPCC and γ. In the initial time of every line cycle, γ can be detected as well as the grid voltage frequency fPCC in the last cycle. The frequency of iG* in the following cycle can be determined by (15).

\(f_{G_{-} k}=f_{P C C_{-} k-1}-k_{f} \gamma\)       (15)

Where kf is drooping coefficient, and γ is positive when iG leads uPCC. If γ is negative, i.e. uPCC is phase-leading, the frequency of iG* in the next line cycle is greater than the frequency of uPCC according to (15). Thus, γ is decreased in next line cycle. Finally, γ trends to zero. When γ is positive, the operation process can be interpreted in a similar way. Following the function of (15), the current iG is in phase with uPCC in steady state without any phase difference.

In order to realize fast phase-tracking, the drooping coefficient kf should be well designed. The detailed design process can be seen in [20], and its expression is:

\(k_{f}=\frac{f_{G}}{2 \pi}\)       (16)

In order to ensure the stability of phase-tracking, kf should be less than the expression in (16).

B. Essence of the FD-PLL

From γ and fPCC, the frequency of iG* in next line cycle can be achieved. Then, at any time tx, the amount of the phase difference reduction can be expressed as:

\(\begin{aligned} \Delta \theta &=\int_{t 0}^{tx} 2 \pi\left[f_{P C C_{-} k}-f_{G_{-} k}\right] d t \\ &=\int_{t 0}^{tx} 2 \pi\left[f_{P C C_{-} k}-\left(f_{P C C_{-} k-1}-k_{f} \gamma\right)\right] d t \end{aligned}\)       (17)

where t0 is the initial time of a line cycle. In the steady state, the frequency in the two adjacent line cycles can be viewed as equivalent. Therefore:

\(f_{P C C_{-} k}=f_{P C C_{-} k-1}\)       (18)

\(\Delta \gamma=\int_{t 0}^{tx} 2 \pi k_{f} \gamma d t\)       (19)

It can be shown that the shrinking of γ (θlag) is the product of 2πkf and the integral of the last γ changing with time. Therefore, the essence of the FD-PLL is a phase adjustment control outer-loop, where the feedback variable is γ and the reference value γ* is zero. An equivalent control block diagram is shown in Fig. 5(b).

C. FD-PLL IDM

The phase difference γ (θlag) can be eliminated by using a FD-PLL. If islanding occurs, γ (θlag) trends to zero since γ(θlag) is a closed-loop feedback parameter as shown in Fig. 5(b).

Thus, paralleled RLC loads whose resonant frequency is within the normal frequency range (49.3-50.5) regardless of the quality factor Qf, are all located in the NDZ (the zones between the dash lines L1 and L2 in Fig. 3). In this case, the NDZ is too large.

According to (3) and (15), the current reference of the improved SMS IDM is:

\(i_{G_{-} k}^{*}=I_{G}^{*} \sin \left[2 \pi\left(f_{P C C_{-} k-1}-k_{f} \gamma\right) t+\theta_{\mathrm{SMS}}\right]\)       (20)

After using (20), the NDZ is in accordance with the normal analysis. However, the disturbed phase angle θSMS still affects the quality of the grid current due to the phase changing caused by the frequency fluctuation. The IDM proposed in this paper modulates the phase angle disturbance into frequency regulation to realize a small NDZ, which can avoid the phase hopping of the reference grid current and improve the power quality of the grid current. The reference current of the proposed IDM is:

\(\begin{array}{l} i_{G_{-} \text {DFPLL_k}}^{*}=I_{G}^{*} \sin \left\{2 \pi\left[f_{P C C_{-} k-1}-k_{f}\left(\gamma-\theta_{\text {SMS }}\right)\right] t\right\} \\ \quad=I_{G}^{*} \sin \left(2 \pi f_{F D P L L} t\right) \end{array}\)       (21)

The method in (21) is a FD-PLL IDM. Eq. (21) only adjusts the frequency, which is different than that of the frequency regulation mode in the SFS IDM. In the SFS IDM, the current reference holds zero for a time interval during every positive and negative half cycle. However, the frequency regulation in (21) is similar to that of the frequency drooping control in a microgrid [22] and the reference current is a continuous sinusoidal waveform.

According to (21), (γ - θSMS) becomes the closed-loop controlled parameter. Thus, (γ - θSMS) must equal to zero in the steady state. Therefore:

\(-\theta_{\text {load}}=-\arctan \left[Q_{f}\left(\frac{f_{r}}{f}-\frac{f}{f_{r}}\right)\right]=\gamma=\theta_{\text {SMS}}\)       (22)

The NDZ of the FD-PLL IDM can be obtained according to (22), which is same as that of the SMS IDM analyzed in [15] if θlag=0. Although the two IDMs have the same NDZs, the FD-PLL IDM eliminates the effect of the lagging phase angle and improves the power quality of the grid current, which is discussed in Section IV.

IV. POWER QUALITY ANALYSIS OF THREE DIFFERENT IDMS

A. Dynamic Response Condition

According to Eqns. (3), (9) and (21), Fig. 6 shows an example of the reference current dynamic regulation process of three IDMs when the utility grid frequency fluctuates in the grid-connected mode. Before ta, the utility grid frequency is at the rated frequency fG. There is no disturbance at this moment according to (4) and (21). For the sake of a convenient analysis, assume the utility grid frequency becomes fPCC1 (>fG) in two successive line cycles after ta.

E1PWAX_2019_v19n2_509_f0006.png 이미지

Fig. 6. Reference currents and their spectrums in the dynamic regulation process of three IDM methods with the same NDZ. (a) Dynamic waveforms. (b) SFS IDM. (c) SMS IDM. (d) FD-PLL IDM.

According to the mathematic relationship in Fig. 6(a), the reference equation can be obtained. Equations (23), (24) and (25) are the reference currents of the SFS, SMS, FD-PLL IDMs, respectively.

\(i_{G_{-} S F S}^{*}=\left\{\begin{array}{ll} -\sin \left(2 \pi f_{G} t\right) & t \in\left(0, \frac{1}{2 f_{P C C 1}}\right) \\ -\sin \left[2 \pi\left(f_{P C C 1}+\Delta f\right) t-\frac{\Delta f \pi}{f_{P C C 1}}\right] & t \in\left(\frac{1}{2 f_{P C C 1}}, \frac{1}{f_{P C C 1}}-t_{z}\right) \\ 0 & t \in\left(\frac{1}{f_{P C C 1}}-t_{z}, \frac{1}{f_{P C C 1}}\right) \end{array}\right.\)       (23)

\(i_{G_{-} S M S}^{*}=\left\{\begin{array}{ll} -\sin \left(2 \pi f_{G} t+\frac{f_{G}}{f_{P C C 1}} \pi-\pi\right) & t \in\left(0, \frac{1}{2 f_{P C C 1}}\right) \\ -\sin \left(2 \pi f_{P C C 1} t+\theta_{S M S}\right) & t \in\left(\frac{1}{2 f_{P C C 1}}, \frac{1}{f_{P C C 1}}\right) \end{array}\right.\)       (24)

\(i_{G_{-} F D P L L}^{*}=\left\{\begin{array}{ll} -\sin \left(2 \pi f_{G} t+\frac{f_{G}}{f_{P C C 1}} \pi-\pi\right) & t \in\left(0, \frac{1}{f_{G}}-\frac{1}{2 f_{P C C 1}}\right) \\ -\sin \left(2 \pi f_{F D P L L} t\right) & t \in\left(\frac{1}{f_{G}}-\frac{1}{2 f_{P C C 1}}, \frac{1}{f_{P C C 1}}\right) \end{array}\right.\)       (25)

It can be seen that there is phase hopping in the SFS and SMS IDMs. Meanwhile, in the FD-PLL IDM, the phase changes continuously.

In order to compare the power quality of the three IDMs, the NDZ of these IDMs should be consistent. If the three IDMs have the same NDZ, (26) must be satisfied.

\(\theta_{\mathrm{SFS}}=\theta_{\mathrm{SMS}}\)       (26)

Table II shows a set of data, which nearly meets (26).

TABLE II DATA SET WITH THE SAME NDZ

E1PWAX_2019_v19n2_509_t0002.png 이미지

In Fig. 6(b) to Fig. 6(d), waveforms and spectrums of the reference current of the three IDMs are plotted according to (23), (24) and (25), respectively. It can be seen that the FD-PLL IDM proposed in this paper has the smallest THD value under the condition of the same NDZ. Therefore, the proposed IDM has the highest power quality in terms of the dynamic process.

B. Steady State

When compared with the dynamic process, the reference currents of the three IDMs in the steady state are relatively simple. It is assumed that the frequency of the grid voltage in the steady state is fPCC. Eqns. (27) and (28) show the reference current expressions when fPCC is greater than or less than the rated frequency under the SFS IDM control.

\(i_{\text {GSFS }}^{*}=\left\{\begin{array}{ll} I_{\text {GSFS }}^{*} \sin \left[2 \pi\left(f_{P C C}+\Delta f\right)\right] t & t \in\left(0,0.5 /\left(f_{P C C}+\Delta f\right)\right) \\ 0 & t \in\left(0.5 /\left(f_{P C C}+\Delta f\right), 0.5 / f_{P C C}\right) \\ -I_{\text {GSFS }}^{*} \sin \left[2 \pi\left(f_{P C C}+\Delta f\right)\right]\left(t-0.5 / f_{P C C}\right) & t \in\left(0.5 / f_{P C C}, 0.5 / f_{P C C}+0.5 /\left(f_{P C C}+\Delta f\right)\right) \\ 0 & t \in\left(0.5 / f_{P C C}+0.5 /\left(f_{P C C}+\Delta f\right), 1 / f_{P C C}\right) \end{array} f_{P C C}>f_{G}\right.\)       (27)

\(i_{G_{-} S F S}^{*}=\left\{\begin{array}{ll} I_{G S F S}^{*} \sin \left[2 \pi\left(f_{P C C}+\Delta f\right)\right] t & t \in\left(0,0.5 / f_{P C C}\right) \\ -I_{G S F S}^{*} \sin \left[2 \pi\left(f_{P C C}+\Delta f\right)\right]\left(t-0.5 / f_{P C C}\right) & t \in\left(0.5 / f_{P C C}, 1 / f_{P C C}\right) \end{array} f_{P C C}<f_{G}\right.\)       (28)

where \(\Delta f=\frac{k \cdot f_{P C C}\left(f_{P C C}-f_{G}\right)}{2-k\left(f_{P C C}-f_{G}\right)}.\)

According to the abovementioned analysis, the reference currents of the SMS IDM and FD-PLL IDM are equal in the steady state. In other words, the phase angle at the end of the last cycle is equal to the phase angle at the beginning of the next cycle. There is no phase hopping in the steady state under the control of the SMS IDM. The reference current is a continuous function and it is expressed as:

\(i_{G S M S}^{*}=i_{G F D_{-} P L L}^{*}=I_{G}^{*} \sin \left(2 \pi f_{P C C} t+\theta_{S M S}\right)\)       (29)

According to (27), (28) and (29), the THD values of the reference current under the three IDMs are shown in Fig. 7. It can be seen that there is almost no distortion when the inverter is controlled by the SMS and FD-PLL IDMs. However, the quality of the grid current with the control of the SFS IDM deteriorates when fPCC is far from the rated frequency and the distortion degree is proportional to the drift value.

E1PWAX_2019_v19n2_509_f0007.png 이미지

Fig. 7. Reference current THD values of the three IDMs in the steady state.

V. SIMULATION AND EXPERIMENTAL VERIFICATION

Simulation models of the three IDMs are built using MATLAB/Simulink with the data listed in Table II and a 2kW prototype is established. Not all of the theoretical analysis is verified by experimental results due to laboratory limitations.

Fig. 8 shows frequency varying experimental curves of the three IDMs with the load listed in Table I after islanding occur. All three IDMs can detect the islanding promptly and accurately.

E1PWAX_2019_v19n2_509_f0008.png 이미지

Fig. 8. Frequency changing experimental curves of three IDMs after islanding occurs. (a) SFS. (b) SMS. (c) FD-PLL.

If the utility frequency is at its rated value, no disturbances are added into the grid reference current for the three IDMs. Thus, the power qualities of the grid currents are the same when fPCC = fG. However, the power quality changes if the utility grid frequency deviates from its rated value. Fig. 9 shows experimental waveforms of grid currents controlled by the different IDMs when the utility grid frequency is operated at 50.4Hz, which is located in the normal frequency range. It can be seen that grid current quality of the inverter controlled by the SFS IDM is heavily affected by utility grid frequency deviations. There is almost no low-order harmonics in grid currents in the SMS and FD-PLL IDMs. In addition, the THD value (4.7%) is mostly from harmonics near the switching frequency. In the SFS IDM, the disturbance parameter is the length of the zero current. The reference grid current is distorted when the utility grid frequency deviates from its rated value. Meanwhile, in the SMS IDM, the disturbance parameter is the phase angle of iG* and the value of iG* at the end of the last cycle is equal to the value of iG* at the initial time of the next cycle. In the FD-PLL IDM, the phase of iG* is not determined by the utility voltage, and iG* is designed continuously in two neighboring line cycles.

E1PWAX_2019_v19n2_509_f0009.png 이미지

Fig. 9. Experimental waveforms of the grid current of three IDMs when the utility grid frequency operates at 50.4Hz. (a) SFS. (b) SMS. (c) FD-PLL.

Fig. 10 shows simulation spectrums of grid currents for the different IDMs with the load listed in Table I when the utility grid frequency hops from 50Hz to 50.4Hz. The power quality of the SMS IDM is heavily affected by frequency hopping. The SFS IDM comes in second and the power quality of FD-PLL IDM appears to be less effected by frequency hopping. The cause and changing processing are analyzed in Section IV, and the simulation results are consistent with the analysis results.

E1PWAX_2019_v19n2_509_f0010.png 이미지

Fig. 10. Waveforms and spectrums of the grid current of three IDMs when the utility grid frequency has a pop change. (a) SFS. (b) SMS. (c) FD-PLL.

A summary of the simulation results for the three IDMs is shown in Fig. 8 and Fig. 9. The FD-PLL IDM proposed in this paper, has the best grid current quality when compared with the SMS IDM and the SFS IDM, regardless of the steady state or dynamic process.

According to the analysis in Section II, the detecting time delay or control parameter effect results in the NDZ error to the SFS and SMS IDMs. However, the phase difference between the grid current and the PCC voltage is detected and it is controlled by a closed-loop. Therefore, the FD-PLL IDM has immunity to the phase detecting delay or control parameter effect. If the load parameter is located in the error zone, for example, fr=50.2Hz and Qf=5 (the error point in Fig. 3), the SFS and SMS IDMs cannot detect islanding when θlag=2°. However, the FD-PLL can detect islanding regardless of the time delay in the phase detecting process. Fig. 11 shows the frequency varying curves of the three IDMs with θlag=0°or θlag=2°, which is the same as the theoretical analysis.

E1PWAX_2019_v19n2_509_f0011.png 이미지

Fig. 11. Frequency varying experimental curves of three IDMs with or without a time delay. (a) SFS. (b) SMS. (c) FD-PLL.

When compared with the SFS and SMS IDMs, the FD-PLL IDM has the best performance, regardless of the islanding detecting accuracy or grid current quality.

VI. CONCLUSION

The conventional frequency disturbance methods, SMS and SFS IDMs, have a number of shortcomings such as an error detecting NDZ and low power quality. In order to overcome these shortcomings, this paper presents a new IDM based on the FD-PLL, which can overcome the effects of both the phase detection delay and control parameter variations. It can also realize unity power factor at the PCC. The emphasis of this paper is to compare the performance of the proposed IDM with those of existing IDMs. The proposed FD-PLL IDM has the best dynamic performance according to the THD values of a SPGCI under the condition of the same NDZ. The FD-PLL and SMS IDMS have the same steady performance. However, the SFS IDM has the worst performance, regardless of the dynamic or steady performance. Moreover, the FD-PLL IDM can solve the error NDZ problem caused by the phase detection delay or control parameter effect. Simulation and experimental results verify the analysis in this paper. The new FD-PLL IDM can be adopted in renewable energy generation systems.

ACKNOWLEDGMENT

This work was supported by National Nature Science Foundation of China (Grant No.51577164), the Fifth ‘333 Project’ in Jiangsu Province, ‘Six Talent Peaks Project’ in Jiangsu Province(XNY-045) and ‘Qinglan Project’ in Jiangsu Province.

References

  1. IEEE Recommended Practice for Utility Interface of Photovoltaic (Pv) Systems, IEEE Std 929-2000, 2002.
  2. IEEE Standard Conformance Test Procedures for Equipment Interconnecting Distributed Resources with Electric Power Systems, IEEE Std 1547.1-2005, 2005.
  3. Q. Wang, M. Cheng, Y. Jiang, W. Zuo, and G. Buja, “A simple active and reactive power control for applications of single-phase electric springs,” IEEE Trans. Ind. Electron., Vol. 65, No. 8, pp. 6291-6300, Aug. 2018. https://doi.org/10.1109/TIE.2018.2793201
  4. X. Xu, X. Zhou, Y. Ma, and Y. Liu, “Research and stability analysis of active-disturbance-rejection-control-based microgrid controllers,” J. Power Electron., Vol. 17, No. 6, pp. 1611-1624, Nov. 2017. https://doi.org/10.6113/JPE.2017.17.6.1611
  5. M. E. Ropp, M. Begovic, A. Rohatgi, G. A. Kern, R. H. Bonn, and S. Gonzalez, “Determining the relative effectiveness of islanding detection methods using phase criteria and nondetection zones,” IEEE Trans. Energy Convers., Vol. 15, No. 3, pp. 290-296, Mar. 2000. https://doi.org/10.1109/60.875495
  6. S. H. Lee and J. W. Park, “Improvement on stability and islanding detection performances by advanced inverter control of DG',” IEEE Trans. Power Syst., Vol. 28, No. 4, pp. 3954-3963, Apr. 2013. https://doi.org/10.1109/TPWRS.2013.2262716
  7. S. H. Lee and J. W. Park, “New islanding detection method for inverter-based distributed generation considering its switching frequency,” IEEE Trans. Ind. Appl., Vol. 46, No. 5, pp. 2089-2098, May 2010. https://doi.org/10.1109/TIA.2010.2049727
  8. H. Laaksonen, “Advanced islanding detection functionality for future electricity distribution networks,” IEEE Trans. Power Del., Vol. 28, No. 4, pp. 2056-2064, Apr. 2013. https://doi.org/10.1109/TPWRD.2013.2271317
  9. C. R. Aguiar, R. F. Bastos, A. F. Q. Goncalves, R. Neves, G. B. Reis, and R. Q. Machado, “Frequency fuzzy antiislanding for grid-connected and islanding operation in distributed generation systems,” IET Power Electron., Vol. 8, No. 7, pp. 1255-1262, Jul. 2015. https://doi.org/10.1049/iet-pel.2014.0624
  10. D. A. Kaiser and J. F. Kaiser, "Estimation of power systems amplitudes, frequencies, and phase characteristics using energy operators," in IEEE Energy Conversion Congress and Exposition Conf., pp. 930-937, 2012.
  11. C. Hou and Y. Chen, “Active anti-islanding detection based on pulse current injection for distributed generation systems,” IET Power Electron., Vol. 6, No. 8, pp. 1658-1677, Aug. 2013. https://doi.org/10.1049/iet-pel.2012.0542
  12. H. Geng, D. Xu, B. Wu, and G. Yang, “Active islanding detection for inverter-based distributed generation systems with power control interface,” IEEE Trans. Energy Convers., Vol. 26, No. 4, pp. 1063-1072, Apr. 2011. https://doi.org/10.1109/TEC.2011.2159720
  13. Y. Wang, H. Jiang, and P. Xing, “Strategy for the seamless mode transfer of an inverter in a master-slave control independent microgrid,” J. Power Electron., Vol. 18, No. 1, pp. 251-265, Jan. 2018. https://doi.org/10.6113/JPE.2018.18.1.251
  14. H. H. Zeineldin, “A Q-f droop curve for facilitating islanding detection of inverter-based distributed generation,” IEEE Trans. Power Electron., Vol. 24, No. 3, pp. 665-673, Mar. 2009. https://doi.org/10.1109/TPEL.2008.2008649
  15. L. A. C. Lopes and H. Sun, “Performance assessment of active frequency drifting islanding detection methods,” IEEE Trans. Energy Convers., Vol. 21, No. 1, pp. 171-180, Jan. 2006. https://doi.org/10.1109/TEC.2005.859981
  16. F. Liu, Y. Kang, S. Duan, and X. Lin, “Improved SMS islanding detection method for grid-connected converters,” Inst. Energy Technol., Renew. Power Gen., Vol. 4, No. 1, pp. 36-42, Jan. 2010.
  17. K. Lim and J. Choi, “Output voltage regulation for harmonic compensation under islanded mode of microgrid,” J. Power Electron., Vol. 17, No. 2, pp. 464-475, Mar. 2017. https://doi.org/10.6113/JPE.2017.17.2.464
  18. H. H. Zeineldin and M. M. A. Salama, “Impact of load frequency dependence on the NDZ and performance of the SFS islanding detection method,” IEEE Trans. Ind. Electron., Vol. 58, No. 1, pp. 139-146, Jan. 2011. https://doi.org/10.1109/TIE.2009.2033482
  19. H. Vahedi and M. Karrari, “Adaptive fuzzy sandia frequency-shift method for islanding protection of inverterbased distributed generation,” IEEE Trans. Power Del., Vol. 28, No. 1, pp. 84-92, Jan. 2013. https://doi.org/10.1109/TPWRD.2012.2219628
  20. J. Kan, N. Li, Z. Yao, Y. Xue, and D. Wu, "Droop PLL for grid-connected inverter," in IEEE Power Electronics and Motion Control Conf., IPEMC, pp. 2183-2186, 2012.
  21. A. Luo, Y. Chen, Z. Shuai, and C. Tu, “An improved reactive current detection and power control method for single-phase photovoltaic grid-connected DG system,” IEEE Trans. Energy Convers., Vol. 28, No. 4, pp. 823-831, Apr. 2013. https://doi.org/10.1109/TEC.2013.2277658
  22. Y. Li and C. Kao, “An accurate power control strategy for power-electronics-interfaced distributed generation units operating in a low-voltage multibus microgrid,” IEEE Trans. Power Electron., Vol. 24, No. 12, pp. 2977-2988, Dec. 2009. https://doi.org/10.1109/TPEL.2009.2022828