Study on Performance Evaluation of Oscillating Heat Pipe Heat Exchanger for Low Temperature Waste Heat Recovery

  • Bui, Ngoc-Hung (School of Mechanical Engineering, Pukyong National University) ;
  • Kim, Ju-Won (School of Mechanical Engineering, Pukyong National University) ;
  • Jang, In-Seung (Department of Air Conditioning Ref. & Sanitary Systems, Yangsan College) ;
  • Kang, Jeong-Kil (Department of Air Conditioning Ref. & Sanitary Systems, Yangsan College) ;
  • Kim, Jong-Soo (School of Mechanical Engineering, Pukyong National University)
  • Published : 2003.06.01

Abstract

The performance of heat exchanger using oscillating heat pipe (OHP) for low temperature waste heat recovery was evaluated. OHP used in this study was made from low finned copper tubes connected by many turns to become the closed loop of serpentine structure. The OHP heat exchanger was formed into shell and tube type. R-22 and R-141b were used as the working fluids of OHP with a fill ratio of 40 vol.%. Water was used as the working fluid of shell side. As the experimental parameters, the inlet temperature difference between heating and cooling water and the mass velocity of water were changed. The mass velocity of water was changed from 30 kg/$m^2$s to 92 kg/$m^2$s. The experimental results showed that the heat recovery rate linearly increased as the mass velocity and the inlet temperature difference of water increased. Finally, the performance of OHP heat exchanger was evaluated by $\varepsilon$-NTU method. It was found that the effectiveness would be 80% if NTU were about 1.5.

Keywords

References

  1. Akachi, H., 1994, Looped capillary tube heat pipe, Proceedings of 71th General Meeting Conference of JSME, Vol. 3, No. 940, pp. 606-611
  2. Akachi, H., Polasek, F. and Stule, P., 1996, Pulsating heat pipes, Proceedings of 5th Int. Heat Pipe Symposium, Melbourne, pp. 208-217
  3. Kim, J. S., Lee, W. H., Lee, J. H., Jung, H. S., Kim, J. H. and Jang, I. S., 1999, Flow visualization of oscillating capillary tube heat pipe, Proceeding of Thermal Engineering Conference of KSME, pp. 65-70
  4. Lee, W. H., Jung, H. S., Kim, J. H. and Kim, J. S., 1999, Flow visualization of oscillating capillary tube heat pipe, 11Ith International Heat Pipe Conference, Tokyo, Japan, Vol. 2, pp. 131-136
  5. Kays, W. M. and London, A. L., 1987, Compact Heat Exchangers, pp.11-78
  6. Huang, B. J. and Tsuei, J. T., 1985, A method of analysis for heat pipe heat exchangers, Int. J. Heat & Mass Transfer, Vol. 28, No. 3, pp. 553-562
  7. Dunn, P. D. and Reay, D. A., 1995, Heat Pipes, Pergamon
  8. Heish, S. S., Liah, C.T. and Han, W. H., 1998, Thermal performances of heat exchangers applicable to waste heat recovery systems, Applied Energy, Vol. 29, pp. 191-200
  9. Lee, Y. and Bedrossian, A., 1978, The characteristics of heat exchangers using heat pipes or thermosyphons, Int. J. Heat & Mass Transfer, Vol. 21, pp. 221-229
  10. Hewitt, G. F., Shires, G. L. and Batt, T. R., 1994, Process Heat Transfer, CRC Press, pp. 73-92
  11. Hewitt, G. F., Shires, G. L. and Polezhaev, Y. V., 1997, International Encyclopedia of Heat & Mass Transfer, CRC Press, New York, pp. 551-555
  12. Im, Y. B., Lee, J. H., Lee, W. H., Kim, J. H.and Kim, J. S., 1999, Influence of working fluid on heat transfer characteristics of heat exchanger using oscillating capillary tube heat pipe for low temperature waste heat recovery, Proceedings of SAREK Summer Meeting, Vol. I, pp. 89-94
  13. Ahn, Y. T., Lee, W. H., Lee, J. H., Kim, J. H. and Kim, J. S., 1999, A study on the performance of oscillating heat pipe heat exchanger for low temperature waste heat recovery, Proceedings of KSME Autumn Meeting, Vol. B, pp. 418-422